Earth resistance tester for checking earthing systems
The battery-powered UNI-T UT521 earth resistance tester is intended for checking the earthing of power networks, lightning protection installations and electrical equipment. 2-wire measurement suits quick checks, and the 3-wire method gives more precise results.

Ranges and accuracy
The range is selected manually with the rotary switch: 20 Ω, 200 Ω or 2000 Ω. In the 200 Ω and 2000 Ω ranges the accuracy is ±(2% + 3), in the 20 Ω range ±(2% + 10). Earth voltage accuracy is ±(1% + 4).

Indicators and protection
The screen has separate symbols for poor contact and over-range (OL). The HOLD/SAVE button holds the reading on screen and saves it to memory. The housing is double insulated.
Screen, power and lid
The backlit LCD screen shows up to 2000 counts. It runs on 6 LR6 batteries (1.5 V), and a screen symbol warns of low battery. The tester switches itself off after about 10 minutes of inactivity. A red lid covers the screen and buttons.

In the box
- UNI-T UT521 earth resistance tester
- Batteries
- Straight test leads with crocodile clips
- Standard test leads with crocodile clips
- Earth spikes
- Carry bag
- User manual







Reviews
There are no reviews yet.